4Ć16 DCP Configuration
Original Ć June 1990CE4.2:CL6211
Restart from Last SP Ċ This configuration item allows the use of the
Restart SP value after a power fail has occurred. If NO is selected, the
restart SP value defined in the Restart SP configuration item is used. If
YES is selected, the last SP value prior to power fail is restored upon
restart.
Restart Ratio Ċ Defines the initial value of the ratio after a power fail
restart, if the Restart from Last Ratio enable configuration item is
answered NO. The valid range is 0.02 to 50.0; this parameter is
unit-less, and can be changed using DDP #32, RST RAT.
Restart SP Ċ Used to define the initial value of the SP after a power fail,
if the Restart from Last SP enable configuration item is answered NO.
The valid SP range is -13.97 to 113.97 percent of the engineering unit
span. The restart SP value may be changed using DDP #30, RST SP.
Signal Select Ċ This Signal Selector PCA configuration item determines
whether the selected signal will correspond to the highest or the lowest
implied valve position (IVP). When the signal selector is in the automatic
mode, the signal present at the selected input is transferred to the
output. A HIGH signal selector selects the input that will cause the
highest IVP; LOW selects the lowest IVP. The selection is based on the
increase open/close setting for the Direct Control point, i.e., a HIGH
selector will select the input that will result in the largest IVP for an
increase-open valve, or the input that will result in the lowest IVP for an
increase-close valve. In an override scheme, all Direct Control points
connected to the signal selector and the signal selector inputs must have
increase open valve action.
SP High Limit Ċ The set point high limit is the highest set point that can
be selected for the Direct Control point. set point high limit is expressed
in engineering units and must be between -13.97 and 113.97 percent of
the engineering unit span. The limit may be changed by tuning DDP
#17, SP HI LM.
SP Low Limit Ċ The set point low limit is the lowest set point that can
be selected for the Direct Control point. set point low limit is expressed
in engineering units and must be between -13.97 and 113.97 percent of
the engineering unit span. The limit may be changed by tuning DDP
#16, SP LO LM.
SP Tracks PV in Manual Enable Ċ Permits the set point to track the
process variable when the Direct Control point is in the manual mode.
This will cause the set point to identically match the process variable
within the limits established by the SP high and low limits.
SP Velocity Limit Ċ Limits the internal SP value used by the Direct
Control Point for control and alarming to a maximum rate of change,
when the point is in AUTO mode. The valid range is any floating point
value in the range 0.0 to 976.369 EUs per minute. The limit may be
changed by tuning DDP #15, SP VL LM.