Response Electronics CL6011B Especificaciones Pagina 153

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 320
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 152
4Ć71FST Configuration
Original Ć June 1990 CE4.2:CL6211
EUP EUP
28
INSTRUCTION NAME: EUP (engineering units to percent conversion)
DESCRIPTION: This instruction converts an engineering-unit SVA input value to percent of
span based on the engineering units high value (EUHV) and the engineering units low value (EULV)
contained in operand 1. The SVD input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
INPUT
OUTPUT
t
0
t
4
t
0
t
4
50
EULV
EUHV
EU
!
%
CONFIGURATION FORMAT: EUP (
Eng conversion factors >>
Comment >>
OPERAND DESCRIPTIONS:
Eng conversion factors - The name of the direct control point (DCP), indirect control point (ICP),
or auxiliary engineering unit pair that contains the engineering units high and low values.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = [(SVA(in) - EULV)/(EUHV - EULV)] X 100%
SVD(out) = SVD(in)
Where: EULV = Engineering units low value
EUHV = Engineering units high value
Vista de pagina 152
1 2 ... 148 149 150 151 152 153 154 155 156 157 158 ... 319 320

Comentarios a estos manuales

Sin comentarios