4Ć151FST Configuration
Original Ć June 1990 CE4.2:CL6211
STAT STAT
89
INSTRUCTION NAME: STAT (station)
DESCRIPTION: This instruction designates the location in the FST where the station type is
executed. When this function is performed, the parameters defined during the station definition
phase of configuration are used to produce the SVA output. STAT is always used with CNTRL or
%CNTRL functions, and it is used only once per loop or not at all. The SVD output is set to 1 if alarm
A is in alarm. Otherwise, it is set to 0.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
A
ALARM
A
A
T
CONFIGURATION FORMAT: STAT (
Comment >>
OPERAND DESCRIPTIONS:
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = f(STAT)
If alarm A is in alarm
Then SVD(out) = 1
If alarm A is not in alarm
Then SVD(out) = 0