Response Electronics CL6011B Especificaciones Pagina 128

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 320
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 127
4Ć46 FST Configuration
Original Ć June 1990CE4.2:CL6211
AOUT AOUT
11
INSTRUCTION NAME: AOUT (analog output)
DESCRIPTION : The analog output will be 4 to 20 milliamps or 1 to 5 volts dc for an SVA input
span of 0 to 100 percent, depending upon which output channel number is selected. The SVA
and SVD inputs remain unchanged. Therefore, the SVA input is available for use in the next
function.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
t
0
t
1
INPUT
t
0
t
1
OUTPUT
20 mA
4 mA
(1 VDC)
(5 VDC)
f (x)
CONFIGURATION FORMAT: AOUT (
AOUT channel >>
Comment >>
OPERAND DESCRIPTIONS:
AOUT channel - The channel number of the desired analog output. The type and number of
outputs for each controller are as follows:
AOUT channel number
Controller type 1 2 3 4 5 6
Computing (1) CO+(2) VO+(2)
2-Wide CO1+ CO2+ VO1+
3-Wide Discrete CO1+ CO2+ VO1+
3-Wide Analog CO1+ CO2+ VO1+ CO4+ VO2+
4-Wide CO1+ CO2+ VO1+ CO3+ CO4+ VO2+
(Continued on next page)
Vista de pagina 127
1 2 ... 123 124 125 126 127 128 129 130 131 132 133 ... 319 320

Comentarios a estos manuales

Sin comentarios