3Ć15 Theory of Operation: Point Processing
Original Ć June 1990 CE4.2:CL6211
GF=1
GF>1
1>GF>0
0% 100%
Valve Position
Lower
Break
Point
Upper
Break
Point
Figure 3Ć6. Implied Valve Position Adaptive Gain
Discrete Adaptive Gain Ċ The Discrete Adaptive Gain Modifier (DAGM)
FST instruction will change the loop's active gain based on the value of a
discrete register or loadable function and the value of the discrete gain
factor. The discrete adaptive gain factor will be set equal to the discrete
gain factor when the discrete value is equal to one. The discrete
adaptive gain factor will be set equal to the unity gain when the discrete
value is equal to zero. Figure 3Ć7 illustrates the operation of the discrete
adaptive gain function. See the FST Section for more information on the
DAGM instruction.
GF=1
GF>1
1>GF>0
Discrete
Input
Time'0' '1'
Figure 3Ć7. Discrete Adaptive Gain
3.3.1.9 Control Sequence with and without Bias
The Control Sequence PCA provides a limited set of functions upon
which a user-defined algorithm may be based. The Control Sequence
PCA provides display and communications interface for the loop, and
also calculates the difference between the loop's process variable and
set point. Valve increase open/close adjustment, trip points for alarms A,
B, C, and D, and set point high/low limits are also provided.