4Ć106 FST Configuration
Original Ć June 1990CE4.2:CL6211
IFTRSP IFTRSP
52
INSTRUCTION NAME: IFTRSP (if true set remote set point mode)
DESCRIPTION: This instruction places the loop being executed into the remote set point mode if
the discrete value in operand 1 is 1. If the discrete value is 0, the mode will not change. The SVA
input remains unchanged. Refer to section 5.6 on page 5Ć9 for more information on using this
instruction.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
RSP A
M
T
OPERAND 1
NO GRAPHIC REPRESENTATION
RSP
CONFIGURATION FORMAT: IFTRSP (
Logic signal >>
Comment >>
OPERAND DESCRIPTIONS:
Logic signal - The name of the general register or discrete loadable function that contains the
discrete value.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVD(out) = SVD(in)
If discrete value = 1
Then mode = remote set point
If discrete value = 0
Then mode = no change
SVA(out) = SVA(in)