4Ć172
Target Data Configuration
Original Ć June 1990CE4.2:CL6211
Sample Interval Ċ The sample interval is the rate at which this point will
send its operating data to the target devices if the reporting mode is
Periodic. Valid entries for this field are 0, 0.5, 1, 3, 5, 10, 15 and 60
seconds.
Type Ċ This read-only field displays the device type of the target
device. This field aids in identifying specific revision levels or names of
devices the point is being targeted to.
4.7.1.1 UOC Target Data Configuration Items
The UOC TARGET DATA form is used to define items related to targeting
a point to a UOC, IFC, or MUX device. If extended alarms or
pressure/temperature compensation are enabled for the target point, the
associated form under the Extra Data" menu option must be completed.
These functions may be enabled for the target point even though they
are not valid for the IAC and Computing Controllers.
Only the fields on the UOC TARGET DATA form that are valid for the IAC
and Computing Controllers are described below.
Current? Ċ This field is set to YES if the device specified by the
configuration Device on the same row is in the current target device
group. A target device group is composed of all of the PROVUEs,
controllers, and CHIPs that have the same Reporting Mode, Sample
Interval and Dead zone, and within the device type have the same field
values (other than DBI or index values). A target device group may
consist of up to 32 devices.
Generally, if YES appears next to a device in the Device field on any set
of the targeting forms, then the data currently displayed applies to that
device. Any change to a target value affects all devices in the Device
field marked as YES. This is a readĆonly field which is defined on the
TARGET DATA form.
Deadzone Ċ The deadzone value indicates the amount by which the PV
must change before the point will be updated at the console if the
Reporting Mode is set to Exception. This is a readĆonly field which is
defined on the TARGET DATA form.
Device Ċ This refers to the name of the device to which the point is to
be targeted. This is a scrolled list of all the devices to which the point is
being targeted. This is a readĆonly field which is defined on the TARGET
DATA form.
Rate Filter Enable Ċ When the rate filter is enabled, momentary
variations in RAV will be smoothed out using a firstĆorder filter. Enabling
the rate filter function also allows the filter time constant to be entered.
The Rate Function Enable configuration item must be set to YES before