Response Electronics CL6011B Especificaciones Pagina 124

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 320
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 123
4Ć42 FST Configuration
Original Ć June 1990CE4.2:CL6211
ALMLD ALMLD
8
INSTRUCTION NAME: ALMLD (alarm monitor load)
DESCRIPTION: This instruction sets the SVD output to 0 or 1 depending on the state of the alarm
monitor contained in operand 2. If the state of the alarm monitor is '0', then the SVD (out) is '0'. If
the state of the alarm monitor is '1', then the SVD (out) is '1'. The direct control point (DCP)
associated with the alarm monitor is contained in operand 1. The SVA input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
DCP - OPERAND 1
REGISTER
ABCD
OPERAND 2
T
CONFIGURATION FORMAT: ALMLD (
Loop tag >>
Alarm number >>
Comment >>
OPERAND DESCRIPTIONS:
Loop tag - The tag name of the loop associated with the alarm monitor.
Alarm number - The number designator that identifies the alarm type, as follows:
1 - Deviation alarm (A)
2 - High or low alarm (B)
3 - High or low alarm (C)
4 - User defined alarm (D)
Comment - A comment up to 255 characters long.
(Continued on next page)
Vista de pagina 123
1 2 ... 119 120 121 122 123 124 125 126 127 128 129 ... 319 320

Comentarios a estos manuales

Sin comentarios