4Ć21DCP Configuration
Original Ć June 1990 CE4.2:CL6211
Increase to Close Ċ Establishes the relationship between the output
current and the implied valve position. When YES is selected, an
increase in implied valve position causes a decrease in output current,
opening an increase-to-close valve. When NO is selected, an increase
in the implied valve position causes an increase in the output current,
opening an increase-to-open valve. The YES/NO selection may be
changed using DDP #10, INC CLO?
IVP High Limit Ċ Limits the maximum IVP value regardless of the mode
of the Direct Control point. When the IVP reaches this limit on a PI_PID_I
Direct Control point, the integral action is disabled to prevent windup.
Implied valve position is expressed as a percent, and may be tuned
using DDP #19, VO HI LM.
IVP Low Limit Ċ This is the same as the IVP high limit configuration
item, except it sets the low limit. The IVP low limit may be tuned using
DDP #18, VO LO LM.
PCA Type Ċ The PCA of the Direct Control point determines the
algorithm that will be used to process the PV. The PCA is defined on the
Direct Control Point form, and is displayed here for reference only.
Restart from Last IVP Ċ This configuration item allows the use of the
restart IVP value after a power fail has occurred. If NO is selected, the
restart IVP value defined in the restart IVP configuration item is used. If
YES is selected, the last IVP value prior to power fail is restored upon
restart.
Restart from Last Mode Ċ This configuration item allows the use of the
restart Mode after a power fail has occurred. If NO is selected, the
restart mode defined in the restart Mode configuration item is used. If
YES is selected, the last Direct Control point mode prior to power fail is
restored upon restart.
Restart IVP Ċ Defines the initial value of the IVP after a power fail, if the
restart from last IVP enable configuration item is answered NO. The
restart IVP is expressed as a percent, and may be changed using DDP
#29, RST VO.
Restart Mode Ċ Defines the initial Direct Control point mode after a
power fail, if the restart from last mode enable configuration item is
answered NO. The restart Mode may be any mode available with the
station type selected. The restart mode for the Direct Control point may
be changed using DDP #28, RST MD.
SP Tracks PV in DDC Mode Enable Ċ Causes the set point to track the
process variable when the Direct Control point is in the DDC mode. YES
enables set point tracking; NO disables it.
Station Type Ċ The station type of a Direct Control point primarily
determines who controls the Direct Control point set point and where the
set point originates. The PCA is defined on the Direct Control Point form,
and is displayed here for reference only.