4Ć155FST Configuration
Original Ć June 1990 CE4.2:CL6211
TIFDDC TIFDDC
93
INSTRUCTION NAME: TIFDDC (true if direct digital control mode)
DESCRIPTION: This instruction sets the SVD output to 1 if the mode of the direct control point
(DCP) contained in operand 1 is direct digital control (DDC). If the mode is not direct digital control,
the SVD output is 0. The SVA input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
T
CONFIGURATION FORMAT: TIFDDC (
Loop tag >>
Comment >>
OPERAND DESCRIPTIONS:
Loop tag - The tag name of the loop containing the DCP mode. The mode is recalled from the
mode status operating data register for the specified loop.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If DCP mode = direct digital control
Then SVD(out) = 1
If DCP mode <> direct digital control
Then SVD(out) = 0
SVA(out) = SVA(in)