4Ć92 FST Configuration
Original Ć June 1990CE4.2:CL6211
HSM HSM
40
INSTRUCTION NAME: HSM (high signal monitor)
DESCRIPTION: This instruction compares the SVA input to the analog value contained in
operand 1. If the SVA input is greater than the analog value, the SVD output is 1. If the SVA input is
less than or equal to the analog value, the SVD output is 0. The SVA input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
100
0
INPUT
1
0
OUTPUT
t
0
t
1
tt
32
SVA (IN)
OPERAND 1
OPERAND 1
t
0
t
1
tt
32
H/
HIGH
SET POINT
VALUE
CONFIGURATION FORMAT: HSM (
Reference value >>
Comment >>
OPERAND DESCRIPTIONS:
Reference value - The name of the general register or analog loadable function that contains the
analog value.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If SVA(in) > Analog value
Then SVD(out) = 1
If SVA(in) <= Analog value
Then SVD(out) = 0
SVA(out) = SVA(in)