4Ć11DCP Configuration
Original Ć June 1990 CE4.2:CL6211
4.3 Direct Control Point Configuration
The Interactive and Computing Controllers provide control of continuous
processes through the use of Direct Control Points. The major
components of each Direct Control Point are:
H Primary Control Algorithm (PCA)
H Station Type
H FST (a series of auxiliary loop functions)
The PCA contains all of the intelligence necessary to transform the loop's
inputs into outputs. The station type is used to define the modes of
operation that are valid for the point. The FST functions define the
control sequence and are used to connect the various input and output
channels to the specific control functions that the user has selected.
A total of six forms are used in defining Direct Control Points. The
configuration items for these forms are described in the following
sections.
4.3.1 Direct Control Point Definition
Description Ċ The description of the point may be up to 16 characters
in length. The first 12 characters will appear on the faceplate display of a
console on the line immediately below the point tag. All 16 characters
may be used on a custom display. Any printable character may be used
in the description.
Device Ċ This is the tag of the Interactive or Computing controller
device on which this Direct Control Point resides. This is a read-only
field.
EU Descriptor Ċ The engineering units descriptor identifies the units of
the device or measured variable being controlled. Examples of this are
% OPEN or GPM. Units may be up to six characters in length.
High Scale Value Ċ The High Scale Value represents the 100-percent
value of the process variable, in engineering units. The valid range for
high scale value is any floating point number; however, it may not be the
same as the low scale value. Select the level in engineering units
corresponding to the maximum expected value of the process variable.
This configuration item may be changed using DDP #2, EU 100%.
Index Ċ The point index for this Direct Control Point. Normally, the first
point configured on the device is given the index 1, the next point 2, etc.
Computing Controllers may have 2 DCPs. 2-Wide IACs and 3-Wide
IACs with Discrete I/O may have 4 DCPs. 3-Wide IACs with Process I/O
and 4-Wide IACs may have 8 DCPs.