4Ć94 FST Configuration
Original Ć June 1990CE4.2:CL6211
ICPLDA ICPLDA
(Continued from previous page)
OPERAND DESCRIPTIONS:
ICP tag - The tag of the ICP.
ICP reg number - The number of the ICP operating data register that contains the ICP value. Two
registers are available and are specified as follows:
ICP Type
Register Type Register No.
Monitor Monitor 1
Reference Reference 1
Monitor- Monitor 1
Deviation Monitor 2
Reference- Monitor 1
Deviation Reference 2
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = (ICP value) [(EUHV - EULV)/100] + EULV
SVD(out) = SVD(in)
Where: EULV = Engineering units low value
EUHV = Engineering units high value