4Ć23DCP Configuration
Original Ć June 1990 CE4.2:CL6211
BIAS Ċ If the BIAS of the indicated DCP is to appear on the detail
display of this DCP, choose YES. Otherwise, choose NO.
RATIO Ċ If the RATIO of the indicated DCP is to appear on the detail
display of this DCP, choose YES. Otherwise, choose NO.
4.3.6 DCP Register DDP Definition
This portion of configuration selects the registers to be displayed on the
system console (or a hand-held tuner) as a detail display parameter
(DDP). A detail display is available for each point configured in the
controller. For each detail display containing direct control point (DCP)
data, any or all of the registers may be selected to appear in the display.
PCA Type Ċ This is a read-only field displaying the PCA type of the
DCP for which the register DDPs are being defined.
Station Type Ċ This is a read-only field displaying the Station type of
the DCP for which the register DDPs are being defined.
No. Ċ This is a read-only field displaying the number of the general
register. For a computing controller the number is 1 through 24. For an
interactive controller the number is 1 through 49.
Register v Ċ The name of the general register as defined previously in
the FST registers definition with a maximum length of 8 characters.
Format Ċ This field determines the portion of the register that is to be
displayed as a DDP. Choose between ANALOG, DISCRETE or BOTH.