4Ć177Target Data Configuration
Original Ć June 1990 CE4.2:CL6211
Sample Interval Ċ The sample interval is the rate at which this point will
send its operating data to the target devices. This is a readĆonly field
which is defined on the TARGET DATA form.
Scale Ċ Identifies the percent of span representing full scale on the
deviation bar in the overview display. The valid range is any number
between 1 and 100.
Suppress Local Alarm Ċ This field determines if this point will have
alarms suppressed. YES prevents alarm messages from being displayed
at the console for this point. Selecting YES will also cause ALMSUP" to
be displayed in the status block of the faceplate for this point. NO
causes the console to process alarms normally using alarm priority, PPA
State and PMA mode information. This field may be tuned via local
PROVUE DDPs.
Suppress Operator Change Ċ This field determines whether the
operator will be able to change the operating parameter of this point from
the console. YES disables operating parameter changes, NO enables
them. Selecting YES also causes OPCSUP" to be displayed in the
status block of the faceplate for this point. This field may be tuned via
local PROVUE DDPs.
Suppress Message Ċ This field determines whether this point will have
alarm messages printed on the printer. Selecting YES will disable alarm
message printing and cause MSGS" to be displayed in the status block
of the faceplate for this point. NO enables alarm message printing based
on alarm priorities, PPA state and PMA mode information. This field may
be tuned via local PROVUE DDPs.
Suppress Operator Change Message Ċ This field determines whether
this point will have operator change messages printed on the printer.
Selecting YES will disable operator change message printing and cause
OPMSGS" to be displayed in the status block of the faceplate for this
point. NO enables operator change message printing. This field may be
tuned via local PROVUE DDPs.
Unit Point Ċ Identifies whether this point should be attached to a unit
point for the purpose of monitoring alarms for a batch end log. Only
points which are unique to a particular unit point should use this field.
Selecting YES allows entering the tag of a unit point. The local PROVUE
database for the specified unit point is where this point's alarm data will
be stored. Selecting NO disables the ability to store alarm data for batch
end logs.
Unit Point v Ċ Identifies the tag of the unit point where this point's alarm
data will be stored. The alarm data may be used for printing out batch
end logs whenever the specified unit is in use.