4Ć7Device Definition Configuration
Original Ć June 1990 CE4.2:CL6211
Strategy Ċ The strategy field is a 12 character text field that can be used
to help group points together. For example, if the plant consists of a
boiler, a reactor, and a tank, the strategy field of each point could be set
to either "Boiler", "Reactor", or "Tank". This data is not checked or
processed in any way, but points can be sorted by the strategy field.
4.2.1 FST Registers
This portion of configuration defines the general purpose registers to be
used by the function sequence table (FST) of the controller.
Number Ċ This is a read only field that indicates the number of the
general register within the controller. For the computing controller this
field is 1 through 24. For the interactive controller this field is 1 through
49.
Register name Ċ The name of the register, up to eight characters in
length. Since each register is identified by its name, each name must be
unique for the controller.
Type v Ċ The register types are MONITOR, REFERENCE, or MONITOR
REFERENCE. This determines the kind of access allowed to the register
by the function sequence table (FST) of the controller or by the operator
interface device (console or hand-held tuner). Table 4Ć1 lists the three
types of registers and shows the access allowed for each. For example,
a monitor register can be written into (data store) or read by (data load)
the controller, but the operator interface can only read it.
Table 4Ć1. Access to Register Types
Controller Access Operator Interface Access
Type of Register Read Write Read Write
Monitor x x x Ċ
Reference x Ċ x x
Monitor-Reference x x x x
Analog Ċ The initial analog value of the register. This value can be any
valid floating point number.
Discrete Ċ The initial discrete value of the register. Choose between
ON and OFF. ON corresponds to a high value or a 1, and OFF
corresponds to a low value or a 0.
Vista de pagina 88