4Ć77FST Configuration
Original Ć June 1990 CE4.2:CL6211
FDFWM FDFWM
(Continued from previous page)
OPERAND DESCRIPTIONS:
Multiplier enable - A tuning parameter that enables or disables the multiplier input (operand 4).
(YES = enable, NO = disable).
Multiplier gain - A tuning parameter that determines the multiplier gain. Gain values are from 0 to
10.00.
Multiplier REV/DIR - A tuning parameter that affects the polarity of the multiplier value (operand
4). (DIR = no change, REV = 1.0 - operand 4).
Multiplier value - The name of the general register or analog loadable function that contains the
analog value for the multiplier input.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If operand 1 = YES, and operand 3 = DIR
Then SVA(out) = SVA(in) X operand 2 X operand 4
If operand 1 = YES, and operand 3 = REV
Then SVA(out) = SVA(in) X operand 2 X (1 - operand 4)
SVD(out) = SVD(in)