3Ć16 Theory of Operation: Point Processing
Original Ć June 1990CE4.2:CL6211
The Control Sequence PCA allows the user to customize the PCA
computation to perform any unique control algorithm. A minimum set of
standard features are provided by the CONTROL and STATION FST
function blocks when the Control Sequence PCA type has been
selected. These standard features include Operating Parameter display
and communications support (PV, SP, IVP, Mode, Bias, and Ratio),
parameter limiting, alarming, tracking, etc.
3.3.1.9.1 FST Configuration using Control Sequence PCA
The user may program any set of computations between the CONTROL
and STATION FST blocks, using the standard FST functions. This is
different from the normal" PCA types, which will NOT allow the user to
program any FST functions between the CONTROL and STATION FST
blocks. These configuration restrictions are as follows:
Standard PCA Types Control Sequence PCA Types
CNTRL
STAT
Only feedforward
FST function blocks
allowed here.
CNTRL
STAT
Any FST function
EXCEPT feedforward
allowed here.
Notice that the FST will not allow the user to configure any feedforward
FST function block into this loop when the Control Sequence PCA type is
selected. The user must accommodate any feed forward action required
by including the FST logic necessary to support that feed forward action.
3.3.1.9.2 Equations for CONTROL FST Function Block
The Signal Value Analog (SVA) output of the CONTROL FST function
block for a Control Sequence PCA type is equal to the loop deviation
error (PV minus SP for direct action, or SP minus PV for reverse action).
The SVA output value is always a percent deviation signal, computed
after the PV and SP have been converted to percent on the Engineering
Units scale. The Signal Value Discrete (SVD) output of the CONTROL
FST function block is set to zero when the PCA is being initialized (such
as after a power fail restart, or after any mode change is received), and is
set to one whenever the PCA is performing all normal forward
Vista de pagina 35