3Ć18 Theory of Operation: Point Processing
Original Ć June 1990CE4.2:CL6211
3.3.2.1 Modes
Manual Mode (MAN): In MAN mode, the operation of the Primary
Control Algorithm (PCA) is suspended, and the operator is allowed to
adjust the IVP. If output tracking is enabled, and output tracking override
in manual mode is enabled, the IVP is dictated by the track signal value.
If the set point tracking in manual mode option is enabled, then the
operator entered SP is overridden by the track signal value. Note that the
set point has no effect on the IVP. The bias value can also be changed.
Automatic Mode (AUT): While in AUT mode, the set point and the bias
(if applicable) are entered by the operator. All of the functions associated
with the PCA are then executed, which determines the final IVP unless
output tracking is enabled.
Remote Set Point Mode (RSP): RSP mode is similar to AUT in that the
PCA functions, or output tracking if enabled, determine the final IVP. In
RSP mode, the set point is received through a configured analog value,
The bias value can still be entered by the operator.
Supervisory Mode (SUP): The SUP mode is similar to the RSP mode
except that in SUP mode, the set point is received from a host computer.
and is not operator adjustable. The bias value can still be entered by the
operator.
Direct Digital Control Mode (DDC): In DDC mode, the operation of the
PCA is suspended, and a host computer controls the IVP. The operator
can still enter the set point unless the set point tracking in DDC mode is
enabled, in which case the operator entered set point is overridden by
the track signal value.
3.3.2.2 Mode Transfers
When a point is involved in a mode transfer, it is common for some or all
of the operating data to change. The mode transfer logic for each direct
control point guarantees that mode changes are bumpless and
balanceless.
Any Mode to Manual: The present value of the IVP and set point are
maintained until the operator initiates a change, unless Set Point Tracks
PV in MAN mode is enabled.
Manual or DDC to Automatic: The present value of all operating data,
including the set point and IVP, is used to initialize the PCA at the
beginning of the transfer. If enabled, transfer bias ramping begins
ramping the IVP from the value at the time of transfer to the value
calculated by the PCA.