
4Ć20 DCP Configuration
Original Ć June 1990CE4.2:CL6211
at which the notch gain becomes effective. When the current Process
Variable of the loop is between the lower and upper notch break points,
the loop proportional gain is multiplied by the notch ratio value. The
upper notch break point is expressed in engineering units and must be
between -36.0 and 136.0 percent of the engineering unit span. The limit
may be changed by tuning DDP #34, NTC HIBP.
4.3.4 Station Parameters
Alarm A Ċ Alarm A is the deviation alarm for the Direct Control point.
The deviation limit, which defines how far the process variable must vary
from the set point before Alarm A is set, must be configured. The alarm
word that will be displayed at the console when the alarm is set must
also be defined (may be up to eight characters in length). The value
range for the deviation limit is 0 to 136.0 percent of engineering unit
span. The deviation limit may be changed using DDP #11, ALM A TR.
Alarm B Ċ Alarm B is one of two absolute alarms for the Direct Control
point (see Alarm C). The alarm must be configured as either a high or
low alarm. The trip point, which defines when the alarm is set, and the
alarm word (up to eight characters in length) that will be displayed at the
console must also be defined. The value range for the trip point is -16.0
to 136.0 percent of engineering unit span. The trip point may be
changed using DDP #12, ALM B TR.
Alarm C Ċ Alarm C is one of two absolute alarms for the Direct Control
point (see Alarm B). The alarm must be configured as either a high or
low alarm. The trip point, which defines when the alarm is set, and the
alarm word (up to eight characters in length) that will be displayed at the
console must also be defined. The value range for the trip point is -16.0
to 136.0 percent of engineering unit span. The trip point may be
changed using DDP #13, ALM C TR.
Alarm D Ċ Alarm D is a user defined alarm. This alarm can only be
set/reset by the Function Sequence Table (FST). The alarm word (up to
eight characters in length) that will be displayed at the console must be
defined.
Alarm Deadband Ċ The deadband is the amount by which the PV must
move away from a trip point, or by which the deviation limit must move
towards a set point, before the alarm is cleared. The valid range is 0 to
136.0 percent of engineering units span. The deadband may be
changed using DDP #14, ALM DBND.
Comentarios a estos manuales