4Ć174
Target Data Configuration
Original Ć June 1990CE4.2:CL6211
cleared. The valid deadband range for each available point attribute is listed
in Table NO TAG (page NO TAG).
Dev Limit Ċ The deviation limit is the amount by which a value must vary
from the reference value to trigger a deviation alarm. The valid deviation limit
for each available loop point attribute is listed in Table NO TAG (page
NO TAG).
Initially Enabled Ċ A YES response enables the alarms.
HIĆLO Trip / Dev Ref Ċ If the alarm type is a high or low alarm, the value at
which a high or low alarm is triggered. If the alarm type is a deviation alarm,
the base value from which a deviation alarm is measured. The valid trip
point or deviation limit for each available attribute is listed in Table NO TAG
(page NO TAG).
Table 4Ć11. Extended Alarm Attributes for UOC AI and Loop Points
TRIP VALUE and DEV LIMIT Necessary
ATTR REFERENCE VALUE and DEADBAND Conditions
CO1 -13.97-113.97% 0-127.94% Control Output 1 must be HELD IN LOOP.
SP See Note 0-127.94% of EU span
%SP -13.97-113.97% 0-127.94%
PV See Note 0-127.94% of EU span
%PV -13.97-113.97% 0-127.94%
IVP See Note 0-127.94% of EU span
%IVP -13.97-113.97% 0-127.94%
BIAS See Note 0-227.94% of EU span Loop type must be Bias & Gain
BIAS See Note 0-127.94% of EU span Loop type must be P_PD with Bias
%BIAS -113.97-113.97% 0-227.94% Loop type must be Bias & Gain
%BIAS -13.97-113.97% 0-127.94% Loop type must be P_PD with Bias
RAV Any floating point number Any positive F.P. number Rate function must be enabled
Note: The valid range is 13.97% of engineering unit span below the Low Scale Value
(113.97% for BIAS on Bias and Gain PCAs) to 13.97% of engineering unit span
above the High Scale Value. (For example, if Low Scale Value is set to -50.0 and
High Scale Value is set to +50.0, the valid range is -63.97 to +63.97.)
UOC PT Compensation Configuration Items
The PT COMPENSATION form is used to define the information relating
to pressure / temperature (PT) compensation for points being targeted to
a UOC.
Absolute Pressure Conversion Ċ The value required to convert the
gauge pressure to absolute pressure, in engineering units. The
controller uses this value to calculate K for the Ideal Gas equation. The
valid range is any floating point value.