4Ć144 FST Configuration
Original Ć June 1990CE4.2:CL6211
%RSPST %RSPST
82
INSTRUCTION NAME: %RSPST (percent remote set point store)
DESCRIPTION: This instruction stores the SVA input in the remote set point operating data
register of the loop being executed. The SVA and SVD inputs remain unchanged. The remote set
point SVA(in) must be in terms of percent of span for the loop. The remote set point value is stored
only when the loop is in the remote set point mode.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
NO GRAPHIC REPRESENTATION
RSP
REG
CONFIGURATION FORMAT: %RSPST (
Comment >>
OPERAND DESCRIPTIONS:
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
RSP value = SVA(in)
SVA(out) = SVA(in)
SVD(out) = SVD(in)