5-14 Controller Cards
UM4.6:CS6003 Original — December 1991
5.3.1 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltmeter
5.3.2 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the configurable controller card shown in Figure 5-7 or
Figure 5-8 in the test slot labeled CONFIG SVCE XFER IND.
Step 3: If the configurable controller card has a discrete I/O module
shown in Figure 5-9, remove selector plug S1 and connect
the cable labeled CONFIG between the selector plug
receptacle on the discrete I/O module and the calibrator
receptacle labeled CONFIG UMB.
X00821–A
Selector Plug Socket
S1 Selector Plug (In Position A)
P2
P1
Figure 5-9. Type CL6201 Configurable Controller Discrete I/O
Module
Step 4: Set the calibrator ON/OFF switch to ON.
Step 5: Press the calibrator RESET switch. The IN PROGRESS
indicator lights and remains lit until the card self-test is
finished. When finished, the COMPLETE indicator lights. If
the COMPLETE indicator fails to light in one minute, the
configurable controller card requires repair.
Step 6: Ensure the INT/EXT switch is set to INT.
Step 7: Press the CAL LOW switch. The OK indicator of the CAL
STATUS indicators should light. If not, adjust the ZERO (R21)
potentiometer on the configurable controller card to the mid
range of settings over which the OK indicator lights.