4-4 Input and Output Card
UM4.6:CS6003 Original — December 1991
Table 4-1. Calibrator Breakout Terminal Assignments for
Single-Ended Analog Input Cards
Breakout
Terminal
Function
1 Channel 1 Input
2 Input Common
3 Channel 2 Input
4 Input Common
5 Channel 3 Input
6 Input Common
7 Channel 4 Input
8 Input Common
9 Channel 5 Input
10 Input Common
11 Channel 6 Input
12 Input Common
13 Channel 7 Input
14 Input Common
15 Channel 8 Input
16 Input Common
17 +24 volts
18 +24 volts
19 24 volt return
20 24 volt return
Step 13: Set the calibrator ON/OFF switch to OFF.
Step 14: Disconnect the umbilical cable and remove the single-ended
analog input card.
4.1.2 Types DM6312 and DM6322 — Analog Input Cards
(Isolated)
The isolated analog input card is available with one of two input ranges:
1 to 5 volts dc and 0 to 10 volts dc. Depending on the application, the
Type DM6312 Analog Input card can use either card version. The Type
DM6322 Analog Input card uses only the 1 to 5 volt dc version. The
calibration procedure refers to the card versions (1 to 5 volt and 0 to 10
volt) and not individual cards by type number.
4.1.2.1 Overview
Calibration of the isolated analog input card consists of setting a
minimum and maximum voltage input level for each of the four input
4
Comentarios a estos manuales