4-11Input and Output Card
Original — December 1991 UM4.6:CS6003
Table 4-5. Resistor Values for Various Temperature Range RTD Cards
Temperature Range Resistor Value
°F °C R1 (Ohms) R2 (Kilohms) R3 (Kilohms)
Pick No.
–50 to 200 –46 to 93 60.1 5.90 560 A1
100 to 500 36 to 260 100 8.87 360 A2
0 to 1000 –17.8 to 537.8 79.6 19.6 137 A7
(1)
1 to 300 –17.8 to 148.9 79.6 6.49 449 A4
–330 to 140 –201.1 to 60 3.01 10.5 243 A5
–100 to 600 –73.3 to 315.6 61.9 14 285 A6
1. Old style pick was A3 and had different resistance values.
4.1.3.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Decade Resistor
4.1.3.3 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the RTD input card in the calibrator test slot labeled
MUX.
Step 3: Connect the RTD termination card to the connector on the
front of the RTD input card.
Step 4: Turn the calibrator ON.
Step 5: Press the calibrator MUX switch. The calibrator numerical
display shows one of the following:
No Code — The card requires repair; terminate procedure
and obtain a replacement card
0024 — The card has a temperature range of -50
°
F to
200
°
F; continue procedure
0025 — The card has a temperature range of 100
°
F to
500
°
F; continue procedure
0026 — The card is a special temperature range RTD
card; continue procedure
Any Other Code — The card is not an RTD card or it
requires repair; terminate procedure and obtain a
replacement card
Step 6: Press the calibrator AI1 group mode switch.
4
Vista de pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 169 170