4-32 Input and Output Cards
UM4.6:CS6003 Original — December 1991
X00614–A
R5 Channel 1 Zero
R6 Channel 2 Zero
R7 Channel 3 Zero
R8 Channel 4 Zero
R23 Channel 1 Span
R24 Channel 2 Span
R25 Channel 3 Span
R26 Channel 4 Span
Figure 4-10. Analog Voltage and Type DM6421 Analog Current Output
Card
4.2.1.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltmeter
4.2.1.3 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is set to OFF.
Step 2: Insert the analog output card in the calibrator test slot labeled
MUX.
Step 3: Connect the umbilical cable labeled MUX DI/BREAKOUT
between the connector on the front of the analog output card
and the calibrator receptacle labeled BREAK-OUT
CONNECTOR.
Step 4: Turn the calibrator ON.
Step 5: Press the calibrator MUX switch. The calibrator numerical
display should show the card identification code 0002. If no
card identification code appears, the analog output card
requires repair. If another card identification code appears,
the card is not an analog output card or the analog output
card requires repair.
4