4-33Input and Output Cards
Original — December 1991 UM4.6:CS6003
Step 6: Press the calibrator AO group mode switch.
Step 7: Set the calibrator CHANNEL SELECT switch to channel 1.
Step 8: If the card is a voltage output version, connect the voltmeter
between the calibrator breakout terminals listed in Table 4-19
for channel 1. If the card is a current output card, connect the
voltmeter across the calibrator 250 OHM LOAD terminals and
jumper the calibrator breakout terminals for channel 1 to the
calibrator 250 OHM LOAD terminals.
Table 4-19. Calibrator Breakout Terminal Assignments for
Analog Outputs Cards
Breakout Terminal Function
1 Channel 1 Output
2 Common Return
3 Channel 2 Output
4 Common Return
5 Channel 3 Output
6 Common Return
7 Channel 4 Output
8 Common Return
9 No connection
10 No connection
11 No connection
12 No connection
13 No connection
14 No connection
15 No connection
16 No connection
17 +24 volts
18 +24 volts
19 24 volt return
20 24 volt return
Note
Verify analog output card type before calibration.
The voltage output card cannot drive a 250 ohm
load. A current output card will produce very high
readings if it is not loaded.