4-12 Input and Output Card
UM4.6:CS6003 Original — December 1991
Step 7: Set the calibrator CHANNEL SELECT switch to channel 1.
Step 8: Using the terminal assignment list in Table 4-6, jumper
between the channel 1 negative and input common breakout
terminals. Connect the decade resistor between the positive
and negative input terminals for channel 1 on the RTD
termination panel. For accurate calibration, keep all test lead
connections tight.
Table 4-6. Terminal Assignments for RTD Input Card Termination
Panel
Breakout Terminal Function
1 Channel 1 +
2 Input Common
3 Channel 1 –
4 No Connection
5 Channel 2 +
6 Input Common
7 Channel 2 –
8 No Connection
9 Channel 3 +
10 Input Common
11 Channel 3 –
12 No Connection
13 Channel 4 +
14 Input Common
15 Channel 4 –
16 No Connection
17 +24 volts
18 +24 volts
19 24 volt return
20 24 volt return
Step 9: Use the label on the card to identify the card temperature
coefficient and, for the special temperature ranges, the
temperature range. Identify on Table 4-7, the correct set of
resistance values to use with your card. Set the decade
resistor to the resistance indicated for the 0.5 percent of span.
Adjust the ZERO potentiometer for channel 1 until the
calibrator numerical display is 0016.